Simulation and Experimental Analysis of a Solar Driven Absorption Chiller With Partially Wetted Evaporator

Author:

Albers Jan1,Nurzia Giovanni2,Ziegler Felix1

Affiliation:

1. Technische Universität Berlin, Marchstraße 18, D-10587 Berlin, Germany

2. Dipartimento di Ingegneria Industriale, Università degli Studi di Bergamo, Viale Marconi, 24044 Dalmine (BG), Italy

Abstract

The efficient operation of a solar cooling system strongly depends on the chiller behavior under part load conditions, since driving energy and cooling load are never constant. For this reason, the performance of a single stage, hot water driven 30 kW H2O/LiBr-absorption chiller employed in a solar cooling system with a field of 350 m2 evacuated tube collector has been analyzed under part load conditions with both simulations and experiments. A simulation model has been developed for the whole absorption chiller (Type Yazaki WFC-10), where all internal mass and energy balances are solved. The connection to the external heat reservoirs of hot, chilled, and cooling water is done by lumped and distributed UA values for the main heat exchangers. In addition to an analytical evaporator model—which is described in detail—experimental correlations for UA values have been used for the condenser, generator, and solution heat exchanger. For the absorber, a basic model based on the Nusselt theory has been employed. The evaporator model was developed, taking into account the distribution of refrigerant on the tube bundle, as well as the change in operation from a partially dry to an overflowing evaporator. A linear model is derived to calculate the wetted area. The influence of these effects on cooling capacity and coefficient of performance (COP) is calculated for three different combinations of hot and cooling water temperature. The comparison to experimental data shows a good agreement in the various operational modes of the evaporator. The model is able to predict the transition from partially dry to an overflowing evaporator quite well. The present deviations in the domain with high refrigerant overflow can be attributed to the simple absorber model and the linear wetted area model. Nevertheless, the results of this investigation can be used to improve control strategies for new and existing solar cooling systems.

Publisher

ASME International

Subject

Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment

Reference14 articles.

1. Analysis of the Part Load Behaviour of Sorption Chillers With Thermally Driven Solution Pumps;Albers

2. Investigation Into the Influence of the Cooling Water Temperature on the Operating Conditions of Thermosyphon Generators;Albers

3. Kruse, C. -D. , 1999, “Berichtsteil II: Simulation und experimentelle Identifikation des Betriebsverhaltens von kleinen heißwasserbetriebenen Absorptionskältemaschinen,” TU Dresden, Institut für Energietechnik und Fernwärme-Forschungsinstitut, Hannover eV, Koordinierter Schlussbericht AiF Fördernummer 11259 B.

4. ‘The Intertube Falling Film: Part 1—Flow Characteristics, Mode Transitions and Hysteresis;Hu;ASME J. Heat Transfer

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3