Affiliation:
1. School of Building Environment Engineering, Zhengzhou University of Light Industry, Zhengzhou 450001, China
Abstract
Fire accidents due to oil-immersed transformers seriously threaten the safe operation of power systems. In this paper, the similarity principle was used to design a high-pressure water mist fire-extinguishing test platform for a small-scale transformer fire, and the design method achieved a good fire extinguishing effect. The results indicate that a deflagration phenomenon, lasting about 2–4 s, could be observed after activating the high-pressure water mist system; the flame temperature rose rapidly at first, then dropped sharply, and finally cooled to the indoor temperature. The nozzle’s flow rate in this system has a significant impact on the fire extinguishing time. Meanwhile, the adjustment of the upper nozzle height also influenced the fire suppression effectiveness of the system, where a height of 1800 mm achieved the best performance compared to the others. In addition, the ambient wind speed is a very unfavorable factor for transformer fire suppression, where the fire extinguishing efficiency decreases rapidly with the increase in wind speed. Therefore, under low wind speed conditions, the high-pressure water mist system has great advantages in the fire suppression of outdoor oil-immersed transformers, and the above research results can provide a reference for the optimization design of this system.
Funder
National Natural Science Foundation of China
Henan Provincial Science and Technology Research Project
Subject
Earth and Planetary Sciences (miscellaneous),Safety Research,Environmental Science (miscellaneous),Safety, Risk, Reliability and Quality,Building and Construction,Forestry
Reference51 articles.
1. Experiments on fire suppression of oil-filled transformer fire;Li;Fire Sci. Technol.,2012
2. Fire and Explosion Risks and Consequences in Electrical Substations—A Transformer Case Study;ASME Open J. Eng.,2022
3. Aspects of Transformer Fires in Brazil;Duarte;Open J. Saf. Sci. Technol.,2012
4. Reflection and Prevention of Transformer Fire Typical Case;Wang;Distrib. Util.,2018
5. Experimental research on factors affecting fire suppression by oil discharge of oil-immersed power transformer;Ma;Ningxia Electr. Power,2020
Cited by
2 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献