Experimental Study on Fire Suppression of the Outdoor Oil-Immersed Transformer by High-Pressure Water Mist System

Author:

Song Huaitao1ORCID,Yao Haowei1,Wei Xiaoge1ORCID,Qin Hengjie1,Li Youxin1,Lv Kefeng1,Chen Qianlong1

Affiliation:

1. School of Building Environment Engineering, Zhengzhou University of Light Industry, Zhengzhou 450001, China

Abstract

Fire accidents due to oil-immersed transformers seriously threaten the safe operation of power systems. In this paper, the similarity principle was used to design a high-pressure water mist fire-extinguishing test platform for a small-scale transformer fire, and the design method achieved a good fire extinguishing effect. The results indicate that a deflagration phenomenon, lasting about 2–4 s, could be observed after activating the high-pressure water mist system; the flame temperature rose rapidly at first, then dropped sharply, and finally cooled to the indoor temperature. The nozzle’s flow rate in this system has a significant impact on the fire extinguishing time. Meanwhile, the adjustment of the upper nozzle height also influenced the fire suppression effectiveness of the system, where a height of 1800 mm achieved the best performance compared to the others. In addition, the ambient wind speed is a very unfavorable factor for transformer fire suppression, where the fire extinguishing efficiency decreases rapidly with the increase in wind speed. Therefore, under low wind speed conditions, the high-pressure water mist system has great advantages in the fire suppression of outdoor oil-immersed transformers, and the above research results can provide a reference for the optimization design of this system.

Funder

National Natural Science Foundation of China

Henan Provincial Science and Technology Research Project

Publisher

MDPI AG

Subject

Earth and Planetary Sciences (miscellaneous),Safety Research,Environmental Science (miscellaneous),Safety, Risk, Reliability and Quality,Building and Construction,Forestry

Reference51 articles.

1. Experiments on fire suppression of oil-filled transformer fire;Li;Fire Sci. Technol.,2012

2. Fire and Explosion Risks and Consequences in Electrical Substations—A Transformer Case Study;ASME Open J. Eng.,2022

3. Aspects of Transformer Fires in Brazil;Duarte;Open J. Saf. Sci. Technol.,2012

4. Reflection and Prevention of Transformer Fire Typical Case;Wang;Distrib. Util.,2018

5. Experimental research on factors affecting fire suppression by oil discharge of oil-immersed power transformer;Ma;Ningxia Electr. Power,2020

Cited by 2 articles. 订阅此论文施引文献 订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献

1. Simulation of fire combustion process in valve hall of DC converter power station;Journal of Loss Prevention in the Process Industries;2024-10

2. Experimental investigation on the suppression characteristics of new natural ester soybean oil transformer fire in room;Ninth International Symposium on Energy Science and Chemical Engineering (ISESCE 2024);2024-06-19

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3