Abstract
Sulfur dioxide (SO2) is a key indicator for fault diagnosis in sulfur hexafluoride (SF6) gas-insulated equipment. In this work, an in situ photoacoustic detection system using an ultraviolet (UV) LED light as the excitation source was established to detect SO2 in high-pressure SF6 buffer gas. The selection of the SO2 absorption band is discussed in detail in the UV spectral regions. Based on the result of the spectrum selection, a UV LED with a nominal wavelength of 285 nm and a bandwidth of 13 nm was selected. A photoacoustic cell, as well as a high-pressure sealed gas vessel containing it, were designed to match the output optical beam and to generate a PA signal in the high-pressure SF6 buffer gas. The performance of the proposed system was assessed in terms of linearity and detection limit. An SO2 detection limit (1σ) of 0.17 ppm was achieved. Additionally, a correction method was supplied to solve PA signal derivation induced by pressure fluctuation. The method can reduce the derivation from about 5% to 1% in the confirmation experiment.
Funder
State Key Laboratory of Power Grid Environmental Protection
Subject
Electrical and Electronic Engineering,Biochemistry,Instrumentation,Atomic and Molecular Physics, and Optics,Analytical Chemistry
Reference23 articles.
1. Partial discharge recognition through an analysis of SF6 decomposition products part 1: Decomposition characteristics of SF6 under four different partial discharges;Tang;IEEE Trans. Dielectr. Electr. Insul.,2012
2. Influence regularity of trace H2O on SF6 decomposition characteristics under partial discharge of needle-plate electrode;Zeng;IEEE Trans. Dielectr. Electr. Insul.,2015
3. Xia, Y., Gong, Y., Tao, H., Wu, L., and Cheng, Y. (2014, January 8–11). Research on arrangement of Ultra High Frequency sensors based on GIS partial discharge. Proceedings of the 2014 ICHVE International Conference on High Voltage Engineering and Application, Poznan, Poland.
4. Analysis of partial discharge Ultrasonic wave characteristic on typical Defects in GIS;Yang;MATEC Web Conf.,2016
5. Murphy, Calculated rate constants of the chemical reactions involving the main byproducts SO2F, SOF2, SO2F2 of SF6 decomposition in power equipment;Fu;J. Phys. D Appl. Phys.,2016
Cited by
6 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献