Author:
Sarasúa José,Martínez-Lucas Guillermo,Platero Carlos,Sánchez-Fernández José
Abstract
Frequency control is one of the most critical tasks in isolated power systems, especially in high renewable penetration scenarios. This paper presents a new hydropower pumped-storage dual control strategy that combines variable-speed-driven pumps and fixed-speed-driven pumps. A possible case for implementation of such a control scheme is described based on El Hierro Island’s power system. This isolated power system consists of a hybrid wind pumped-storage hydropower plant and diesel generators. The pumped-storage power plant is divided into a hydropower plant equipped with four Pelton turbines and a pump station equipped with both fixed- and variable-speed pumps. According to the proposed control scheme, frequency regulation will be provided by a dual controller: a continuous controller for the variable-speed pumps and a discrete controller for the fixed-speed pumps. The Pelton units, which operate as synchronous condensers, also supply the power system inertia. Therefore, diesel units may be disconnected, decreasing generation costs and greenhouse gas emissions. Owing to the combination of both controllers and the inertia of the Pelton units, an acceptable frequency regulation can be achieved. This technique has been validated through computer simulations.
Funder
Ministerio de Economía, Industria y Competitividad, Gobierno de España
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous)
Cited by
27 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献