Abstract
For improving the zero-voltage ride through the capability of a doubly fed induction generator in high proportion new energy grid in extreme faults, a coordinated control scheme of hardware and optimal control strategy is proposed. A high-temperature superconductive-fault current limiter suppresses stator fault current, adaptive virtual impedance control and active dynamic reactive power support control act on the back-to-back converter of wind turbines as optimal control strategies. Optimizing the control strategy without changing the controller structure is beneficial to engineering implementation. After mathematical derivation and simulation verification, the coordinated control strategy adopted in this paper can effectively avoid the rotor current and voltage exceeding the limit when the wind turbine is facing extreme faults, actively provide reactive power support for the busbar, realize zero voltage ride through and reduce the risk of high voltage failure at the point of failure. The control effect is obviously better than the traditional virtual impedance control.
Funder
Science and Technology Research Program of Chongqing Municipal Education Commission
Subject
Management, Monitoring, Policy and Law,Renewable Energy, Sustainability and the Environment,Geography, Planning and Development,Building and Construction
Cited by
1 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献