Affiliation:
1. State Key Laboratory of Electrical Insulation and Power Equipment Xi'an Jiaotong University Xi'an China
2. State Grid Anhui Electric Power Research Institute Hefei China
Abstract
AbstractThe contact finger electrical connection structure is a crucial component of high voltage bushings, and its safety and reliability directly impact the operational stability of the bushing. To investigate electrical contact performance of the contact finger under eccentric conditions, a three‐dimensional electrical, thermal, and force multi‐physics coupling calculation model was established. Additionally, a test platform was constructed to measure electrical contact characteristics of the contact finger. The contact characteristics of the contact finger when the male head was axially deflected and radially offset compared to the female head were obtained. The research findings indicate when the male head deflects axially, the contact force changes of the contact finger blades on both sides are opposite. Moreover, as the axial deflection angle of the male head increases, the resistance of the electrical connection structure shows a rising‐slow decreasing‐fluctuating trend. The resistance is highest at 3°, with a resistance increase rate of 7.35%. Furthermore, the resistance of the electrical connection structure varies with the radial offset of the male head, following a power function. Contact failure occurs when the radial offset is 1.31 mm, and the resistance increase rate reaches 24.9% at a radial offset of 1.58 mm.
Funder
National Natural Science Foundation of China
Publisher
Institution of Engineering and Technology (IET)
Reference25 articles.
1. Causes of abnormal resistance of electrical contact elements in valve side ascending flange of UHV converter transformer;Duan H.;Power Syst. Technol.,2023
2. Israel T. Schlegel S. Großmann S. et al.:Modelling of transient heating and softening behaviour of contact points during current pulses and short circuits.Proc. IEEE Holm Conf. Electrr. Contacts pp.9–18.IEEE Piscataway NJ(2019)
3. Tian H. Jin S. Gong A. et al.:Analysis on the deterioration behavior of electrical contact structure used in converter transformer RIP bushings.Proc. CSEE.41(03) 1146–1156(2021)
4. Corrosion reaction kinetics and high‐temperature corrosion testing of contact element strips in ultra‐high voltage bushing based on the phase‐field method
5. Analysis and field‐repair of current overheating faults on dry type SF6 gas‐insulated valve side bushing in converter transformer;Zhou A.;Power Syst. Technol.,2018